Boiler Fan Power Consumption Saving By Duct
Interconnection Between Hot PA Bed Gun Header
And Upper SA Header
How & why was the problem Furnace I/L air nozzle area 2. Increase in EBIDTA by
identified? with help of Duct Rs. 98 Lacs/year at station
Interconnection between level.
In Boiler, both SA fan current
hot PA Bed Gun Header and
was running higher side and 3. Slight Reduction in APH
Upper SA header thus full
also higher Fan discharge tube leakage due to reduced
utilizing Bed Gun nozzle area
pressure @10-11 KPA. SA Fan Discharge
for combustion.
Header pressure
What was the challenges
Impact of solution to the
encountered?
business? Team Members
Reduction in SA Fan disch
1. Average fan power Sh. Haresh Bhingradiya
header pressure by 1 KPA.
consumption reduction by Sh. Himanshu Patel
And Total Fan current
70 KW per Unit which Sh. Mayank Pathak
reduction by 7 Amp in
resulted in reduction of
each Unit.
Station Auxiliary Power
How was the problem consumption by
solved? 560 KW (0.05%).
Fan disch pressure reduced
by 1 KPA by increasing